Inverter control
- Menu: 4.9.24-3.1-8
- Index: 8706.6[0]
Description
Defines whether the safety option intervenes in the control of the inverter when the safety sub-function is active.
The parameter setting is specified in the Assist CS.. tool. In MOVISUITE®, the specified setting is only displayed. This description refers to the Assist CS.. tool.
The following settings are possible:
Setting | Meaning |
---|---|
Active |
The inverter stops the motor with the defined application limit for deceleration (parameter group Functions > Monitoring functions > Limit values). The limit value specified for the jerk time is additionally used for the jerk-limited ramp. |
Not active | The safety option does not interfere with the inverter control. The inverter is controlled via an external source, such as digital inputs, fieldbus, or system bus. |
Active with limitation |
The inverter stops the motor with the defined application limit for deceleration (parameter group Functions > Monitoring functions > Limit values). The limit value specified for the jerk time is additionally used for the jerk-limited ramp. The deceleration ramp of the inverter is limited to the following values:
|
DefaultSetting
Active