
Sensor supply pulsing
- Menu: 4.9.6-6.1-1
- Index: 8704.7[0]
Description
Specifies whether the supply voltage of the connected sensor technology is pulsed. These test pulses can be used to detect interference voltages and crossfaults on the safe digital inputs F‑DI (Line diagnostics parameter active).
The parameter setting is specified in the Assist CS.. tool. In MOVISUITE®, the specified setting is only displayed. This description refers to the Assist CS.. tool.
The following settings are possible:
Setting | Meaning |
---|---|
Active | The supply voltage of the sensors is pulsed. Line diagnostics can be performed. |
Not active | The supply voltage is not pulsed. If line diagnostics is active, error E‑60.3. Safe digital input: F‑DI 0. Crossfault is triggered. |
DefaultSetting
Active
