Connection type
- Menu: 4.9.6-4.1-2
- Index: 8704.4[0]
Description
Specifies the connection type.
The parameter setting is specified in the Assist CS.. tool. In MOVISUITE®, the specified setting is only displayed. This description refers to the Assist CS.. tool.
The following settings are possible:
Setting | Meaning |
---|---|
1-channel | The two safe digital inputs F‑DI can be used separately as an NC contact or NO contact. |
2-channel equivalent | The logical connection of the two safe digital inputs F-DI has the logical value 1 if the same signals are applied to the two digital inputs. The two safe digital inputs provide either an NC function or an NO function. |
2-channel non-equivalent | The logical connection of the two safe digital inputs F-DI has the logical value 1 if different signals are applied to the two digital inputs. One safe digital input provides an NC function and the other safe digital input provides an NO function. |
DefaultSetting
2-channel equivalent