F-DI 00 & F-DI 01

  • Menu: 4.9.6-4.1

Description

Digital input pair F‑DI of the safety option.

The parameter setting is specified in the Assist CS.. tool. In MOVISUITE®, the specified setting is only displayed. This description refers to the Assist CS.. tool.

The following parameters are set:

Parameter

Meaning

Discrepancy time t2

Time during which the signals of the two safe digital inputs in the two-channel connection types do not have to result in a logically correct signal.

If the time is exceeded, error E-60.2. Safe digital input: F-DI 0./0. Discrepancy error is triggered.

Connection type

Specifies the connection type of the safe digital inputs.

Switch test function

Specifies whether the switch test function is activated.