Response to fast power-off detection

  • Menu: 4.6.9-1.2-1
  • Index: 8351.1

Description

Specifies how the inverter responds to a violation of the limit value specified in the DC link level for fast power-off detection parameter.

The following settings are possible:

Setting

Meaning

No response

The event is ignored.

Application stop + output stage inhibit

The drive stops subject to speed control with the value of the Deceleration parameter (parameter group Monitoring functions > Limit values). The output stage is inhibited when motor standstill is reached. If a brake is installed, it is applied or the DynaStop® function is activated.

Emergency stop + output stage inhibit

The drive stops subject to speed control with the value of the Emergency stop deceleration parameter (parameter group Monitoring functions > Limit values). The output stage is inhibited when motor standstill is reached. If a brake is installed, it is applied or the DynaStop® function is activated.

Output stage inhibit

The output stage is inhibited immediately. If a brake is installed, it is applied or the DynaStop® function is activated. The drive is stopped in a non-controlled manner.

DefaultSetting

Output stage inhibit