Description
Specifies the data source of the analog output. Select the required source from the drop-down menu.
Calculating the output value at the analog output
The physical output value at the analog output (voltage output/current output) is calculated from the quantities without units in the device according to the following formula:
[Output value]  | = V or mA  | 
Raw value  | Source value without units  | 
Conversion factor  | Fixed value: 
  | 
Numerator scaling  | Parameter Numerator scaling  | 
Denominator scaling  | Parameter Denominator scaling  | 
Offset  | Parameter Voltage offset scaling or Current offset scaling  | 
The raw value is the measured source value without units scaled with the number of decimal places:
Source value  | Quantity of parameter Data source without unit  | 
Number of decimal places  | The number of decimal places depends on the position at which the analog setpoint is to be used: 
  | 
Example: Calculating an output voltage
The following quantities are given in the example:
Quantity  | Value  | 
|---|---|
Function of the analog output  | +/- 10 V output  | 
Data source of the analog output  | Actual speed in user units  | 
Current actual speed from the parameter Speed as source value (parameter group Diagnostics > Process values > Active drive train)  | 20.00 rev. min-1  | 
User unit  | Rev. min-1  | 
Number of decimal places  | 2  | 
Conversion factor  | 1000/1 V  | 
Numerator scaling  | 1  | 
Denominator scaling  | 5  | 
Offset (parameter Voltage offset scaling)  | 2.5 V  | 

[Output voltage] = V  | 