Response to encoder fault
- Menu: 4.6.11-5.2-1
- Index: 8622.14
Description
Specifies how the inverter responds to an encoder fault.
The following settings are possible:
Setting | Meaning |
---|---|
Application stop + output stage inhibit | The drive stops subject to speed control with the value of the Deceleration parameter (parameter group Monitoring functions > Limit values). The output stage is inhibited when motor standstill is reached. If a brake is installed, it is applied or the DynaStop® function is activated. |
Emergency stop + output stage inhibit | The drive stops subject to speed control with the value of the Emergency stop deceleration parameter (parameter group Monitoring functions > Limit values). The output stage is inhibited when motor standstill is reached. If a brake is installed, it is applied or the DynaStop® function is activated. |
Output stage inhibit | The output stage is inhibited immediately. If a brake is installed, it is applied or the DynaStop® function is activated. The drive is stopped in a non-controlled manner. |
DefaultSetting
Application stop + output stage inhibit