Response to application heartbeat timeout
- Menu: 4.6.11-3.3-1
- Index: 8622.21
Description
Specifies how the inverter responds to a timeout of the application heartbeat.
The application heartbeat is intended for use with controllers from SEW‑EURODRIVE and is configured via the controllers.
The following settings are possible:
Setting | Meaning |
---|---|
Warning | The inverter does not respond. The fault code is displayed via the display elements of the inverter and is output in process data. |
Application stop + output stage inhibit | The drive stops subject to speed control with the value of the Deceleration parameter (parameter group Monitoring functions > Limit values). The output stage is inhibited when motor standstill is reached. If a brake is installed, it is applied or the DynaStop® function is activated. |
Emergency stop + output stage inhibit | The drive stops subject to speed control with the value of the Emergency stop deceleration parameter (parameter group Monitoring functions > Limit values). The output stage is inhibited when motor standstill is reached. If a brake is installed, it is applied or the DynaStop® function is activated. |
Output stage inhibit | The output stage is inhibited immediately. If a brake is installed, it is applied or the DynaStop® function is activated. The drive is stopped in a non-controlled manner. |
DefaultSetting
Application stop + output stage inhibit