Response to external fault
- Menu: 4.6.11-3.2-1
- Index: 8622.5
Description
Specifies the response of the inverter to an external error.
An external error can be triggered as follows:
- Via a function that is assigned to the digital input (parameter group Inputs/outputs > Basic unit/I/O card)
- Via a bit for the control words (parameter group Setpoints > Control word.)
The signal of the external error is evaluated as 0-active. The response is executed when the output stage is enabled.
The following settings are possible:
Setting | Meaning |
---|---|
No response | The event is ignored. |
Warning | The inverter does not respond. The fault code is displayed via the display elements of the inverter and is output in process data. |
Application stop + output stage inhibit | The drive stops subject to speed control with the value of the Deceleration parameter (parameter group Monitoring functions > Limit values). The output stage is inhibited when motor standstill is reached. If a brake is installed, it is applied or the DynaStop® function is activated. |
Emergency stop + output stage inhibit | The drive stops subject to speed control with the value of the Emergency stop deceleration parameter (parameter group Monitoring functions > Limit values). The output stage is inhibited when motor standstill is reached. If a brake is installed, it is applied or the DynaStop® function is activated. |
Output stage inhibit | The output stage is inhibited immediately. If a brake is installed, it is applied or the DynaStop® function is activated. The drive is stopped in a non-controlled manner. |
DefaultSetting
Application stop + output stage inhibit